3.15.2.1 Configuring the Monitoring Through the EPS30-4815AF
The EPS30-4815AF system converts the input 220 VAC into the -48 VDC to provide the -48
VDC power. In addition, the EPS30-4815AF system can manage one VRLA battery set and
monitor other environment parameters through its EPMU03 monitoring module. This topic
provides the basic information about the EPS30-4815AF and describes how to configure data
associated with environment monitoring.
Prerequisites
l
The EPS30-4815AF must be connected to the ESC port of the control board on the
MA5616 through a straight-through cable.
l
The setting of the hardware DIP switch on the EPS30-4815AF must be the same as the
setting of the EMU subnode in the environment configuration.
l
The sixth DIP switch on the EPS30-4815AF must be set to off, which indicates that the
baud rate is 19200 bit/s.
Context
l
The differences between an analog parameter and a digital parameter are as follows:
–
An analog parameter is a consecutive parameter, such as the temperature, voltage, and
current.
–
A digital parameter is a discrete value that indicates a state.
l
The EPS30-4815AF requires an RS-485 serial port for data communication.
Mapping Between Monitoring Parameters and Device Ports
describes the mapping between the monitoring parameters displayed on the host and
the ports on the sensor transfer box.
Table 3-26
Mapping between the monitoring parameters displayed on the host and the ports on
the sensor transfer box
Monitoring Parameter on Host
Device Port
Temperature
Temperature and humidity
Humidity
Temperature and humidity
Digital 0
JTD1
Digital 1
JTD2
Digital 2
JTD3
Digital 3
JTD4
Digital 4
JTD5
Digital 5
JTD6
Digital 6
JTD7