Step 5
Check whether the dedicated environment monitoring cable connecting the ESCM to the serial
port on the MA5612 is aged, exposed, or broken out.
l
If the dedicated environment monitoring cable connecting the ESCM to the serial port on
the MA5612 is aged, exposed, or broken out, go to
.
l
If the dedicated environment monitoring cable connecting the ESCM to the serial port on
the MA5612 is not aged, exposed, or broken out, go to
.
Step 6
Replace the dedicated environment monitoring cable connecting the ESCM to the serial port on
the MA5612. Run the
display emu
command to check whether the ESCM is in
Normal
state.
l
If the ESCM is in
Normal
state, go to
.
l
If the ESCM is in
Normal
state, go to
.
Step 7
Check whether the settings of the DIP switch on the ESCM are the same as the settings of the
secondary nodes of the EMU on the MA5612.
l
If the settings of the DIP switch on the ESCM are the same as the settings of the secondary
nodes of the EMU on the MA5612, go to
.
l
If the settings of the DIP switch on the ESCM are different from the settings of the secondary
nodes of the EMU on the MA5612, go to
.
Step 8
Set the DIP switch on the ESCM or run the
emu add
command to configure the secondary nodes
of the EMU on the MA5612 again so that the settings of the DIP switch on the ESCM are the
same as the settings of the secondary nodes of the EMU on the MA5612. Run the
display
emu
command to check whether the ESCM is in
Normal
state.
l
If the ESCM is in
Normal
state, go to
.
l
If the ESCM is not in
Normal
state, go to
.
Step 9
Record the results of the preceding steps in a fault report (see Fault Report Form), fill out the
entire form, and then submit it to Huawei for technical support (see
Step 10
End.
----End
7.2 EPS30-4815AF Being in Fault State
The EPS30-4815AF power system is used in the AC-powered cabinet to convert the AC into
the DC and then distribute the power to implement DC power distribution. This document
provides the troubleshooting guide when the EPS30-4815AF is in
Fault
state.
Location Method
The EPS30-4815AF, namely POWER4830, is displayed as Pwr4830 on the MA5612 interface.
When the EPS30-4815AF is in
Fault
state, locate the fault according to the following procedure:
1.
Check whether the serial port mode of the MA5612 is
emu
.
2.
Check whether the sixth switch of the DIP switch on the EPS30-4815AF is set to off (the
baud rate is 19200 bit/s).
3.
Check whether the dedicated environment monitoring cable connecting the EPS30-4815AF
to the serial port on the MA5612 is faulty.
SmartAX MA5612 Multi-service Access Module
Maintenance Guide
7 Troubleshooting EMU Faults
Issue 01 (2012-07-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.