RMS-SNMP01B SNMP Card
User Manual
11 Upgrading the SNMP Card
Issue 10 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
56
Figure 11-5
Upgrade success page
When
Upgrade progress
is
100%
for SNMP card software, log in again if the "Connection with the
UPS failed. Check network connectivity and log in again." message is displayed.
If the upgrade fails and the UPS and the SNMP card do not power off, click
Activate
again to restart the upgrade, as shown in
Figure 11-6
Upgrade failure scenario 1
If a power failure occurs during the upgrade, power on the UPS and SNMP card again. After
you log in to the WebUI again, click
Go to Step 3
to perform the upgrade again, as shown in
(you can skip