Figure 3-58 Connecting the pressure tubes
Step 4 Connect the differential pressure sensor cables to terminals 4, 5, and 6 of X502.
Step 5 Install the fan maintenance baffle plate.
----End
3.6.11 (Optional) Installing a Cap (Applicable to Upflow
Units)
Prerequisites
●
Before installing the cap, attach the thermal insulation foam in the
accessories to the top beam of the smart cooling product, and ensure that the
reserved holes in the thermal insulation foam are aligned with the holes in
the beam. Check that the cap is intact and free from scratches, that the sheet
metal is not bent, and that the screws are secure.
●
Before installing the cap, reserve space on the top of the upflow unit. The
height of the reserved space must be greater than that of the cap.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
83