4.5.4.2 Setting Communications Parameters (Modbus RTU Protocol)
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Figure 4-7 Modbus Settings
Step 2 Set the baud rate, communication address, and RS485 monitoring group. For
.
Table 4-7 Baud rate and communication address settings
Parameter Setting
Setting Method
Baud rate
9600, 19200
Set the baud rate as required. The value should be
consistent with that set on the EMS.
Communic
ation
address
1–255
Set the communication address of the smart
cooling product as planned. The EMS
communicates with the smart cooling product
through this address, and the communication
addresses of two smart cooling products
connecting to the same EMS must be unique.
RS485
monitoring
grouping
Enable,
Disable
● For CAN networking and no grouping scenario,
set the "RS485 monitoring grouping" of the last
smart cooling product to "Enable".
● For CAN networking and grouping scenario, set
the "RS485 monitoring grouping" of the last
smart cooling product in each teamwork
control group to "Enable".
----End
4.5.4.3 Setting Communications Parameters (Modbus TCP Protocol)
Context
This section applies to the scenario where the device is connected to the NMS.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual