3. Check whether the number of standby devices on the topology is the same as
the actual device number.
–
If yes, go to
.
–
If no, check the cable connection and the settings of teamwork control
parameters.
4. Check whether the number of online devices on the topology is the same as
the actual device number.
–
If yes, the check is complete.
–
If no, check the cable connection and the settings of teamwork control
parameters.
4.5.4 Setting Communications Parameters
4.5.4.1 Setting Access Control Parameters
Path: Settings > Comm Settings > Access Control
Figure 4-6 Access Control
Parameter
Description
Remote control
● Enable: Users can control the unit over their
monitoring system.
● Disable: Users cannot control the unit over their
monitoring system.
SSH (LAN)
● Enable: Access to the unit through the intranet using
SSH (default port number: 22) is allowed.
● Disable: Access to the unit through the intranet
using SSH is not allowed.
● If this parameter is set to Disable, the function will
be enabled within 30 minutes after power-on by
default.
● If this parameter is set to Enable, the function will
be automatically disabled after 24 hours of running.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
109