Parameter
Description
Configuration Principle
Max indoor fan speed
Sets the maximum speed
for the indoor fan.
The default value is
100%. You are advised
not to change the value.
----End
4.5.3 Setting Teamwork Control Parameters
Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
●
Teamwork group No.: Group the smart cooling products in adjacent areas as
one, that is, assign one teamwork group number for them. At most four
teamwork control groups can be set (1–4).
●
System address: The address (configurable range: 1–32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data. The recommended value range is 1 to the number of
units in the group.
Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
> Teamwork Settings, to enter the Teamwork
Settings screen, as shown in
.
Figure 4-4 Teamwork Settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Air conditioner address, Enable teamwork CAN
resistor, Teamwork function and Networking mode can be set on slave smart
cooling products. Other parameters of the slave units will be modified by the
master unit synchronously.
describes how to set the parameters.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
4 Power-On Commissioning
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
103