6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
237
6.6 Troubleshooting
Certain circuits in the NetCol8000-C have lethal voltage. Only professional technicians are
allowed to perform maintenance. Exercise caution during live-line troubleshooting.
If jumpers are used for troubleshooting, remove them after troubleshooting. Connected
jumpers may affect control functions and damage equipment.
describes how to troubleshoot the NetCol8000-C.
Table 6-6
NetCol8000-C troubleshooting
Symptom
Possible Cause
Reference Solution
The NetCol8000-C
generates abnormal
sound.
Fans, pipes, or support are loose.
Shock absorption bars between
the unit and the support are lost.
Fix the component and add shock absorption
bars.
An indoor fan fails to
start.
Neither the main circuit breaker
nor the indoor fan circuit breaker
is switched on.
Check that the general switch and fan switch
are ON.
An indoor fan is damaged.
Replace the indoor fan.
The northbound
communication is
abnormal.
The northbound communications
cable is incorrectly connected.
Check that the northbound communications
cable is connected to the northbound
communications port on the main control
module.
The ambient temperature
and humidity sensor
cannot detect the
humidity and
temperature.
Parameter settings on the
controller are incorrect.
Check that the ambient temperature and
humidity sensor is enabled on the controller.
The ambient temperature and
humidity sensor is faulty.
Enable the ambient temperature and humidity
sensor. If the temperature and humidity still
cannot be detected, replace the sensor.
The communications cable to the
temperature and humidity module
is incorrectly connected.
Check that the northbound communications
cable is not connected to the RS485/12 V
port, which is for connecting to the
temperature and humidity sensor, on the front
panel of the main control module.
Condensate water exists
on the surfaces of the
front or rear panel.
The operating environment of the
NetCol8000-C is extremely
humid.
Enhance the airtightness of the equipment
room.
The temperature threshold is set to
a much smaller value.
Adjust the temperature and humidity
thresholds.