NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
144
Figure 4-12
Setting SNMP port
SNMP Port
is set to
161
by default.
Step 6
Tap
Next Page
.
Step 7
Set SNMP trap parameters.
1.
Tap
Add
under
SNMP Trap
.
2.
Set
Trap Address
as planned and
Trap Port
to the actual port number.
Trap Port
is set to null by default.
3.
Select the
SNMP Version
. If an SNMPv3 user is configured, it is recommended that
SNMP Version
be set to
SNMPv3
.
4.
If
SNMP Version
is set to
SNMPv3
, select an
SNMPv3 user name
, and then tap
as shown in
Figure 4-13
Setting SNMP trap parameters