4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
140
Parameter
Setting
Setting Method
address
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when
Link mode
is set to
Client
.
NMS port
number
N/A
It is recommended that you retain the default value. If you
need to change the value, enter a value as required. This
parameter is configurable when
Link mode
is set to
Client
.
----End
4.4.4.3 Setting Communications Parameters (SNMP Protocol)
Context
To set communications parameters, log in as the
admin
user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a smart
cooling product to an EMS (element management system).
One smart cooling product supports concurrent access of up to 6 EMSs through SNMP.
Procedure
Step 1
On the home screen, choose
Settings
>
Comm Settings
>
SNMP Settings
displayed.
Figure 4-6
Setting SNMP communications parameters
Step 2
Set
SNMP Version
based on site requirements, and then tap
Submit
.
If you set
SNMP Version
to
ALL
or
SNMPv1&v2c
, you can set
Read Community
and
Write Community
by performing