NO TE
● If a power failure occurs and the smart cooling product is powered on again, the smart
cooling product automatically restores to the original state (start or shutdown) before
the power failure.
● The hardware port for controlling the status of the remote dry contact or On/Off status
on remote is reserved on the ACC. The status of the remote dry contact and On/Off
status on remote is on by default.
● The operations that start the smart cooling product successfully by the LCD button or by
element management system (EMS) is effective only when the remote dry contact or
On/Off status on remote is on the status of on.
● In start mode, the Start button is green (unavailable) and the Shutdown button is gray
(available).
● In shutdown mode, the Shutdown button is green (unavailable) and the Start button is
gray (available).
----End
5.4.3 Setting Temperature and Humidity Values
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
is displayed.
Figure 5-6 Setting temperature and humidity values
Step 2 Set the parameters by referring to
NO TE
You are not recommended to modify the parameters not listed in
Table 5-2 Parameter description
Parameter
Description
Configuration Principle
T/H control
type
Return-air
Return-air: For a hot aisle, select
Return-air to control the temperature
and humidity around the air return vent
of the smart cooling product.
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
97