NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
29
It is recommended that you close the inlet valve in the unit when there is chilled water
circulation in the system and the unit is not in use.
Figure 3-2
Connection diagram for bottom pipe routing
(1) Copper gate valve
(2) Y-shaped strainer
3.1.3 Material Preparations
Materials are classified to Huawei-provided, self-purchased, and onsite prepared materials,
which are marked as mandatory, optional, and engineering purchasing in this document.
Mandatory: materials that are provided by Huawei and can be found in the delivered
fittings.
Optional: materials that can be purchased from Huawei or any other vendor (if you have
ordered the materials from Huawei, you do not need to purchase them elsewhere). For
details about the specifications of such materials to be purchased, see the following
sections.
Engineering procurement: materials that are not configured by Huawei and need to be
purchased from another vendor.
3.1.3.1 Automatic Drainpipe
The drainpipe supports the rigid pipe connection.