NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
106
During component replacement, do not lean any material against the cabinet.
6.1.2 Routine Maintenance Item
describes the routine maintenance requirements for the NetCol5000-C.
In low temperature areas (< 0°C), close the external water inlet and outlet valves, drain water
in the heat exchanger from the needle valve at the bottom, and take antifreeze measures for
the NetCol5000-C if it will not be used for a long time.
Table 6-1
Routine maintenance
No. Operation
Troubleshooting
Period
Result
1
Check that the air filter
is not blocked by dirt.
Clean or replace the
air filter.
Monthly
□Passed
□Failed
2
Check that the return air
filter is not damaged or
deformed.
Replace the air filter.
Monthly
□Passed
□Failed
3
Check that the exhaust
valve does not leak.
Close the exhaust
valve.
Monthly
□Passed
□Failed
4
Check that screws
fastening the water
sensor are securely
connected.
Secure the screws
tightly.
Monthly
□Passed
□Failed
5
Check that the water pan
filter is clean and not
blocked.
Clean the water pan
filter.
Monthly
□Passed
□Failed
6
Indoor temperature and
humidity (T/H) sensors
are properly installed
and do not drop off.
Secure the T/H
sensors.
Monthly
□Passed
□Failed
7
Choose
Maint
>
Diagnostic Mode
>
Enter
, and set the
chilled water valve
opening to 100%. Check
that the chilled water
valve handle
automatically turns to
the maximum opening.
If the handle of the
chilled water valve
actuator does not
automatically turn to
the maximum, adjust
the actuator to the
maximum (100 %).
Quarterly
□Passed
□Failed
8
Check that no foreign
matter exists in the fan.
Clean the foreign
matters.
Semi-annual
□Passed
□Failed
9
Check that the fan
Repair the fan
Semi-annual
□Passed