10
Troubleshooting
CA UTION
Certain circuits in the smart cooling product have lethal voltages. Only
professional technicians are allowed to perform maintenance.
NO TICE
● Exercise caution during live-line troubleshooting.
● If jumpers are used for troubleshooting, remove them after troubleshooting.
Connected jumpers may affect control functions and damage equipment.
describes how to troubleshoot the NetCol5000-A.
Table 10-1 Troubleshooting
Symptom
Possible Cause
Solution
The unit
generates
abnormal
voice.
The compressor, fan, or pipes
are loose.
Check the fixing structure and
ensure that all components are
securely installed.
The
compressor
does not
work.
The high-pressure switch
reacts.
Check the high-pressure switch
status.
Circuit breakers, fuses, or
cables are disconnected.
Check the main circuit breaker,
compressor circuit breakers,
fuses, and cables.
A compressor motor is
damaged.
Replace the motor.
A compressor does not need
to start.
Check the requirement status on
the display module.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
10 Troubleshooting
Issue 08 (2021-09-17)