NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
31
3.1.2.6 Pipe Support
shows a support for refrigerant pipes and water pipes. The specific support
appearance depends on site situations.
Figure 3-5
Pipe support (unit: mm)
U-shaped pipe clamp height H = Pipe diameter (including the thermal insulation foam) – 5 mm. Pipe
supports are not configured by Huawei.
Stainless steel 304 is recommended for pipe supports and pipe clamps.
Install a support every 1500 mm in straight sections of pipes, and 500 mm away from each bending
point in turning sections.
3.1.2.7 Cable Specifications
The onsite ground resistance must be less than 0.1 Ω.
The fireproof level of the cable must be at least VB.
lists specifications of power cables and cables to the host. The cables must be
protected by a protective tube when connecting the power cables and the external signal
cables.
Table 3-8
Cable specifications
Application
Scenario
Name
Technical Specifications
Description
Indoor unit
Power
cable
(optional)
Active route
with heating
and
humidification
Electrical power cable, 600 V,
ZA-RVV, 5 x 10 mm
2
, black (five
core wires: red, yellow, green, blue,
black), 57 A, outdoor cable, CE
The length is
determined in presale
survey.
Dual-route power
supply: 2 PCS
Single-route
Standby or
without heating
Electrical power cable, 600 V,
ZA-RVV, 5 x 6 mm
2
, black (five