NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
3 Installation Guide
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
28
Temperature
(°C)
Saturation
Pressure-Surface
Pressure (MPa)
Temperature
(°C)
Saturation
Pressure-Surface
Pressure (MPa)
Temperature
(°C)
Saturation
Pressure-S
urface
Pressure
(MPa)
13
1.09
32
1.89
51
3.04
14
1.12
33
1.94
52
3.11
15
1.16
34
1.99
53
3.19
16
1.19
35
2.04
54
3.26
17
1.23
36
2.1
55
3.34
18
1.27
37
2.15
N/A
N/A
3.1.2.2 (Optional) Refrigerant Oil
The recommended refrigerant oil is RL32H/Emkarate. You can purchase it from Huawei or
another vendor. The refrigerant oil purchased from another vendor should be confirmed by
Huawei.
3.1.2.3 (Optional) Oil Trap and Inverted Trap
The operating pressure of the copper pipe, oil trap, and inverted trap should be greater than
4.5 MPa.
Figure 3-2
Oil trap and inverted traps (unit: mm)
Table 3-7
Specifications for oil traps and inverted traps
No.
Name
Copper Pipe Outer
Diameter and
Thickness
Technical Requirements
1
Oil trap
19.1 mm x 1.2 mm
The flaring inner diameter of the copper
pipe is 19.1 mm, and the necking outer
diameter are 16.0 mm.
Содержание NetCol5000-A021
Страница 234: ......