NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
196
Step 6
Reinstall the liquid pipe NTC temperature sensor.
Step 7
Perform a leakage test with nitrogen again.
Step 8
After checking that the smart cooling product does not leak, vacuumize the smart cooling
product and charge refrigerant.
----End
6.5.6 Replacing the Threaded Filter Dryer
Prerequisites
The filter dryer needs to be replaced.
A spare threaded filter dryer of the same model is available and functional.
Tools: refrigerant retrieval device (configured based on local conditions), Phillips
screwdriver, nitrogen cylinder, refrigerant tank, vacuum pump, pressure gauge, leather
hose, protective gloves, two 27# adjustable wrenches, 36# wrench
Preparation: Power off the indoor unit and reclaim all refrigerant from the system.
Context
shows the position of the filter dryer.
Figure 6-12
Position of the filter dryer
(1) Liquid pipe NTC temperature sensor
(2) Pipe nut
(3) Adjustable nut
(4) Filter dryer nut
(5) Filter dryer
(6) Hold hoop