5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
210
Figure 5-60
Installing a switch
Step 7
Reconnect the cables to the switch and reinstall the cover, as shown by (2) and (3) in
Step 8
Install the air filter and close the rear door.
Step 9
Power on the device and tap
Startup
on the home screen. Ensure that the air conditioner is
running normally without any alarms.
----End
5.4.17 Replacing the Contactor
Prerequisites
The dual power switch contactor, AC contactor, or electric heater contactor, as shown in
, needs to be replaced. This part uses KM3 as an example.
A spare contactor of the same model is available and functional.
Tool: Phillips screwdriver
Procedure
Step 1
On the controller home screen, tap
Shutdown
, and turn off the air conditioner switch in the