5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
132
Compone
nt
Item (Monthly
Maintenance)
Troubleshooting
Electric
heater
Start the indoor unit. Choose
Maint
>
Diagnostic Mode
>
Enter
on the main screen, and
set
Electric heater
to
On
.
Check whether the electric
heater generates heat.
NOTE
To avoid burns, do not touch the
electric heater surface with bare
skin.
Replace the electric heater. For details,
refer to
5.1.4 Yearly Maintenance
lists yearly maintenance items for the indoor unit.
Calculate the total cooling capacity and total server load of running indoor units. If the total
load exceeds 80% of the total cooling capacity of the air conditioner, Huawei recommends
increasing the number of air conditioners.
Table 5-4
Yearly maintenance checklist
Compon
ent
Item (Quarterly Maintenance)
Troubleshooting
Sensor
Use a high-precision humidity and
temperature sensor to calibrate the
humidity and temperature sensors
inside and outside the cabinet.
If the temperature deviation is greater
than 1°C or humidity deviation is
greater than 5%, the T/H sensor must
be calibrated or replaced.
calibrate the T/H sensor.
Evaporat
or
The evaporator fins are not pushed
down.
Use a fin brush to organize the fins that
are pushed down.
Welding
spot and
needle
valve
Check that the welding spots and
needle valves do not leak using
soapy water, or check that they are
free from oil stains.
If leaking points are found, retrieve the
refrigerant and weld the leaking points
again. For details, contact Huawei
technical support.
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...