NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
97
4.5.2 Temperature and Humidity Values
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
T/H Sensor
displayed.
Figure 4-11
Setting temperature and humidity values
Step 2
Set the parameters by referring to
You are not recommended to modify the parameters not listed in
Table 4-4
Parameter description
Parameter
Description
Configuration Principle
T/H control
type
Cold-aisle
,
Hot-aisle
,
Return-air
, or
Supply-air
can
be set as required. The
temperature and humidity set
points correspond to the
selected control type can be
set.
Return-air
: Select
Return-air
to
control the temperature and humidity
around the air return vent of the
precision air conditioner.
Supply-air
: Select
Supply-air
to
control the temperature and humidity
around the air supply vent of the
precision air conditioner.
Cold-aisle
: For a cold aisle, select
Cold-aisle
to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
Hot-aisle
: For a hot aisle, choose
Hot-aisle
to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
Temp control
This parameter controls the
Average: Select
Average
if the
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...