Refrigerant Oil
The refrigerant oil, Danfoss 160SZ, is recommended.
●
If the indoor unit code is one of 52270741, 52270742, 52270743, 52270744,
52270745, 52270746, 52270747, and 52270748, additional refrigerant oil =
additional refrigerant charge x 2.5%.
●
If no, charge refrigerant oil as follows:
–
If the low-temperature component is not connected, do not add
refrigerant oil.
–
If the low-temperature component is connected, and L ≤ 10 m, do not
add refrigerant oil.
–
If the low-temperature component is connected, and L > 10 m, additional
refrigerant oil = additional refrigerant charge x 4%.
5.2.2 (Optional) Charging in Refrigerant Oil
Prerequisites
Refrigerant oil is prepared by referring to
5.2.1 Calculation about the Charged
the Refrigerant and Refrigerant Oil
.