Step 4 Click Maint > USB Operations > Remove USB to remove the USB flash drive in
safe mode.
----End
4.6.2.4 Clearing the Runtime
Context
To clear the runtime of the smart cooling product, log in as the Admin or
Engineer user.
NO TICE
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
displayed.
Figure 4-34 Performance maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End
4.6.2.5 Calibrating a Sensor
Context
●
Calibrate a sensor if the displayed temperature or humidity on the sensor
deviates from the actual value. For example, if the return air temperature
measured by other temperature detection devices at the return air detection
point is 20°C while the value measured by the sensor is 22°C, the sensor has
an error of 2°C, and the calibration value should be set to –2°C.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)