NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
43
Move the outdoor unit close to the installation position before unpacking. You are
recommended to stand the outdoor unit during transportation. If tilt is not avoidable, the
tilt degree cannot exceed 15°.
Do not hold the fan guard on the shell. Otherwise, it will be deformed.
Do not touch the blades using hand or any other object.
After installing the outdoor unit, remove the protective cardboard of condenser fin.
Procedure
Step 1
Determine the four mounting holes of the outdoor unit based on the installation dimensions
and drill holes in the concrete base.
Step 2
Align the outdoor unit mounting holes with the holes in the concrete base, and secure the
outdoor unit to the concrete base using four M10 expansion bolts, as shown in
Figure 3-21
Installing an outdoor unit
----End
3.9 Connecting Refrigerant Pipes
Context
Tools: adjustable wrench (250 mm x 30 mm), hex key (5 mm), torque wrench
(17#/19#/27#/30#/36#)