Parameter
Description
Port
Set this parameter to the port through which the device
connects to the collector.
For details about the ports on the ECC800-Pro collector, see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro
.
Device Address
Set this parameter to the address set on the device.
Step 8 Click
on the toolbar to save the device information.
Step 9 Click Connection test to start the connection test.
----End
6.5.3 Adding the Access Management System
6.5.3.1 Setting Monitoring Parameters for the A8802RS Access Controller
Procedure
Step 1 Set the address of the access controller using the DIP toggle switches, set the
device address to 0 by default, as shown in
Table 6-40 Setting the address of the access controller
Device Address
Toggle Switch 1
Toggle Switch 2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
Step 2 Set the baud rate of the access controller to 19200. The preset data bit, stop bit,
and check bit are 8, 1, and none respectively. For ECC800-Pro collector settings,
see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro Collector
----End
6.5.3.2 Creating an Access Controller on the NetEco
This section describes how to create an access controller on the NetEco.
Prerequisites
●
You have the operation rights for Access Control Management and Planning
Configuration.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
258