6.4.5.3 Setting UPS5000 Monitoring Parameters (over SNMP)
Before connecting the UPS5000 to the NetEco, set the IP address on the UPS5000,
and add a user and set permissions on the UPS5000 WebUI.
Prerequisites
●
You have obtained the IP address, subnet mask, and default gateway planned
for the UPS5000.
●
The UPS5000 is powered on.
Context
●
UPS WebUIs may vary slightly depending on the UPS software version.
Perform operations based on the actual WebUI.
●
The non-encryption algorithm used in UPS5000 poses potential risks.
Therefore, exercise caution when deciding to use the non-encryption
algorithm.
Procedure
Step 1 Set the IP address for the UPS5000 on the LUI.
1. Choose System Info > Settings > Comm Settings > IP Settings.
NO TE
The preset password is 000001.
2. Set IP address assign to Manual, and set IP address, Subnet mask,
Gateway, IPv6 Address, and so on.
Step 2 Access the UPS5000 WebUI.
1. On the PC with an IP address in the same network segment as the UPS5000,
type the UPS5000 IP address in the address box of a browser and press Enter.
The UPS5000 IP address is set in
.
2. Enter the user name and password for logging in to the UPS5000 and click
Login.
NO TE
The preset user name and password are admin and Changeme respectively for the
UPS5000.
3. Set user permissions by referring to
based on the site
requirements.
Step 3 Add a user and set user permissions on the WebUI (WebUI 1).
1. Choose System Settings > SNMP Settings.
2. In the SNMP area, set SNMP Version to SNMPv3 and SNMP Port to 161,
and click Submit.
3. In the SNMPv3 area, click Add.
4. In the displayed SNMPv3 dialog box, set SNMPv3 parameters, and click
Confirm.
–
You are advised to set MD5/SHA password and DES/AES password to
different values.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
204