Step 5
Check whether
AI/DI_1 Sensor Type
can be automatically identified. For example,
Smoke
Sensor
is automatically identified, as shown in
Figure 6-56
Setting the sensor type of a dry contact
Step 6
Set
AI/DI_1 Power Supply
to
On
.
Step 7
Click
Submit
.
----End
6.4.2.1.3 Setting Device Monitoring Parameters of an NO/NC Dry Contact on the ECC
After a normally open (NO) or normally closed (NC) dry contact is connected to the AI/DI
port of an ECC500 V6 collector, you need to set device parameters of the NO or NC dry
contact on the WebUI.
Prerequisites
You have obtained the IP address, and login user name and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Context
An NO or NC dry contact is a device whose normal status signal is open (or closed) and
whose alarm signal is closed (or open), such as a skylight controller.
This section describes how to set skylight controller monitoring parameters when a
skylight controller is connected to the AI/DI_1 port of the MUE05A4 card of an ECC500
V6 collector. Set the parameters based on the actual port connected to the skylight
controller onsite.
Procedure
Step 1
Log in to the WebUI of the ECC500 V6 collector.