6.4 Scenarios for Connecting the ECC500 Collector
6.4.1 Commissioning the ECC500 V6 Collector
6.4.1.1 Setting ECC500 V6 Collector IP Address
This topic describes how to configure an IP address and a subnet mask for the ECC500 V6
collector before connecting it to the element management system (EMS).
Prerequisites
You have obtained the IP address (default: 192.168.1.168) for the ECC500 V6 collector.
The browser (Internet Explorer 8.0 or later, Firefox, or Chrome) for logging in to the
ECC500 WebUI is available.
Set the TLS1.1 and TLS1.2 protocols for the browser. Use Internet Explorer 11 as an
example. Open the Internet Explorer, choose
Tools
>
Internet Options
, click the
Advanced
tab, and select
Use TLS1.1
and
Use TLS1.2
.
You have installed hardware for the ECC500 V6 collector and powered it on.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
You have obtained the planned IP address, subnet mask and default gateway for the
ECC500 V6 collector.
Context
A unified IP address (192.168.1.168) is configured for all ECC500 V6 collectors before
delivery. You must reconfigure an IP address for the ECC500 V6 collector as required to
prevent IP address conflict.
Procedure
Step 1
Use a PC that has an IP address in the same network segment with that of the ECC500 V6
collector, enter https://
192.168.1.168
in the address bar, and click
Enter
on the keyboard.
Step 2
(Optional) Install a security certificate when logging in to the page. Click
Continue to this
website (not recommended)
, as shown in
Figure 6-42
Prompt message indicating an incorrect certificate