IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
3 Installation Scenarios in Dual Row Aisle Containment
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
47
No.
Check Item
Result
vertical distances are 2200 mm
(tolerance: ±3 mm).
4
If a support is used, the vertical
distance must also be 2000 mm or
2200 mm between the cabinet top and
the upper surface of the ESD floor.
NA
5
The optimal deviation of vertical
distances is 0 mm between the upper
surface of the ESD floor and the upper
surface of the support. A maximum of
3 mm is acceptable.
NA
6
After leveling cabinets, measure the
height from the ESD floor.
NA
3.4.1 Installing a Sliding Door
Context
shows the structure of a sliding door.
Figure 3-23
Structure