Check the first installed skylight is OK or not by using the following method: Push the skylight to
the horizontal position, and check whether the skylight is within 600 mm of the skylight connective
plates.
Directions of the other skylights follow the direction of the first one. All the skylights installed are
required to face the same direction as the first one.
The gaps between adjacent skylights are 3±1 mm.
If the gaps between the skylights and the skylight connective plates are uneven after the skylights are
installed, adjust the gaps by adjusting the skylight connective plates.
4.
Push the installed flat skylight to the horizontal position, and secure the skylight with a
magnetic lock fastener, as shown in
Figure 3-18
Installing a flat skylight
5.
Secure a magnetic lock electromagnet using M4 screws, as shown in
Figure 3-19
Installing a magnetic lock electromagnet
Step 8
Using M4x12 cross recessed pan head screw assemblies to install the barrier strips for the
control skylight according to the location of barrier strips for the other skylights, as shown in