Procedure
Step 1
Switch off the power circuit breaker of the fire control panel.
Step 2
Open the fire control panel and make a note of the cable connection.
Step 3
Disconnect cables, remove the fire control panel, and remove batteries from the fire control
panel.
Step 4
Install the new fire control panel and connect cables.
Step 5
Install batteries in the lower part of the fire control panel.
Step 6
Install parallel cables for fire control panel batteries, as shown in
Figure 5-54
Connecting battery cables
Step 7
Switch on the power circuit breaker of the fire control panel.
Step 8
Check whether the new fire control panel is working properly.
If the power indicator is on and the alarm indicator is off, the fire control panel is working properly.
----End
Follow-up Procedure
Dispose of the removed fire control panel that is confirmed faulty.
5.4.10 Replacing an Emergency Light
Prerequisites
An emergency light needs to be replaced.
A spare emergency of the same model is available and functional.
Impact on the System
None
Preparations
Tools: screwdriver, step ladder, protective gloves