Step 4
Remove the drive.
1.
Press the ejector release button on the drive panel to release the ejector lever. See (1) in
2.
Open the drive ejector lever completely. See (2) in
.
3.
Holding the ejector lever of the drive, pull out the drive for about 3 cm (1.18 in.). Wait
for at least 30 seconds and remove the drive from the server. See (3) in
.
Do not insert or remove drives frequently. If a drive is frequently removed and installed
in an interval shorter than 30 seconds, there are risks that the drive cannot be identified.
Figure 3-22
Removing a drive
Step 5
Place the removed component in an ESD bag.
Step 6
Install a drive filler.
NOTE
Perform this operation only when a drive is not installed immediately.
----End
3.14 Installing a SAS/SATA Drive
l
The SATA or SAS drives support hot swap. After a faulty drive is disconnected from its
backplane, wait 30 seconds before removing it. The alarm will not be cleared immediately
after a new drive is installed. It will be cleared after the RAID array rebuild is complete.
Do not frequently hot-swap a drive to prevent new alarms.
l
To prevent damage caused by insufficient heat dissipation and high temperature, install
components or filler panels.
FusionServer Pro CH121 V5 Compute Node
User Guide
3 Basic Operations
Issue 06 (2019-08-10)
Copyright © Huawei Technologies Co., Ltd.
47