Installation and Configuration
7.1 Installation Environment Requirements
7.1 Installation Environment Requirements
7.1.1 Space and Airflow Requirements
To allow for servicing and adequate airflow, observe the following space and airflow
requirements:
l
Install the server in an access-restricted area.
l
Keep the area in which the server is located clean and tidy.
l
To facilitate heat dissipation and maintenance, keep a clearance of 800 mm (31.50 in.)
between walls and the front and rear doors of the cabinet.
l
Do not block the air intake vents. Otherwise, air intaking and heat dissipation will be
affected.
l
The air conditioning system in the equipment room provides enough wind to ensure
proper heat dissipation of all components.