FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
A Appendix
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
230
The number of cables and holes shown in the figure is for reference only.
Step 4
Lay out the PDU2000 cables on the top of the cabinet and reinstall the rodent-proof mesh, as
shown in (4) in
Step 5
Connect the PDU2000 cables for other cabinets in the same way.
----End
Follow-up Procedure
Before connecting the power plug of a device to the PDU2000, loosen the locking device on
the PDU2000. After connecting the power plug, tighten the locking device.
A.8 Cable Routes Inside an IT Cabinet
Route cables neatly inside the IT cabinet by following instructions in
Signal cables or weak-current cables inside cabinets are sorted by cable managers, cable rings, and
cable trays.
The cable colors shown in figures are for reference only.
show the routes of the cables out from the front of
customer equipment.
Figure A-40
Cable route along a horizontal cable manager
(1) Small cable ring
(2) Cable manager
(3) Customer equipment