FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
A Appendix
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
208
Figure A-10
Column in a row of cabinets (A < 70 mm and B ≥ 400 mm)
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in
Install cable trays over the cabinets on both sides of the blank cabinet place. If the cable trays cannot
be installed in combined mode, install them in layered mode, the upper for routing weak-current
cables while the lower for routing strong-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in