ECC500
User Manual
5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
60
5.2.3.2 Adding an SPD
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A surge protective device (SPD) should be connected to the AI/DI_2 port on the
MUE05A4 of the ECC500 by default. To connect the SPD to another port, set the port
parameters using the following method.
An SPD is a normally closed (NC) dry contact device. The normal signal status is NC,
and the alarm signal status is normally open (NO).
Procedure
Step 1
Log in to the ECC500 WebUI.
Step 2
Choose
Monitoring
>
MUE05A Expansion Card
>
MUE05A4
>
Running Parameter
>
AI/DI_2 Port Settings
.
Step 3
Set
AI/DI_2 Sensor
to
Enable
.
Step 4
Click
Submit
.
Step 5
Set
AI/DI_2 Sensor Name
, for example, to
SPD
.
Step 6
Set
AI/DI_2 Sensor Type
to
NC
.
Step 7
Set
AI/DI_2 Power Supply
to
On
.
Step 8
Click
Submit
Figure 5-10
Adding an SPD
----End