4 Installation and Commissioning
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
45
Toggles 1 to 6 of the DIP switch specify the device address in binary mode.
ON
indicates
1
,
and
OFF
indicates
0
shows an example of the switch settings.
Table 4-3
Mapping between T/H sensor device addresses and DIP switch settings
Device
Address
Toggle
Switch 1
Toggle
Switch 2
Toggle
Switch 3
Toggle
Switch 4
Toggle
Switch 5
Toggle
Switch 6
Toggle
Switch 7
Toggle
Switch 8
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
----End
4.4.2 Setting the WS332M2-5 T/H Sensor Device Address
Procedure
Step 1
Hold down
SET
on the display panel of the T/H sensor for 2 seconds.
Step 2
When
Add
is displayed, set the device address by pressing
+
and
-
.
----End
4.4.3 Setting the UPS2000-G-A Device Address
Context
UPS2000-G-A V100R001 is used and equipped with an LCD screen, as shown in
Figure 4-25
LCD screen display
Procedure
Step 1
Operate the DIP switch S2 on the optional Modbus card to set the UPS2000-G-A device
address.