7.15 How Can I Set Temperature and Humidity Alarm
Thresholds for a T/H Sensor?
Prerequisites
A T/H sensor has been added to the ECC500.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Procedure
Step 1
Log in to the ECC500 WebUI.
Step 2
Choose
Monitoring
>
Temp/Hum Group
>
Temp/Hum34001
>
Running Parameter
.
34001
in
Temp/Hum34001
is variable and subject to change with the model, connected collector port,
and device address of the T/H sensor. The displayed value prevails.
Step 3
Set
High Temperature Alarm Point
,
Low Temperature Alarm Point
,
High Humidity
Alarm Point
, or
Low Humidity Alarm Point
, and click
Submit