ECC500
User Manual
7 FAQ
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
118
If
DO Settings
is set to
Disable
, the DO port does not take effect.
If
DO Settings
is set to
Association
, the AI/DI alarm is associated with the DO port. If the AI/DI
port reports an alarm, the DO port reacts accordingly.
If
DO Settings
is set to
Manual
, you can select
DO Operation
to change the DO signal status to
control whether the device is running.
----End
7.13 How Can I Change the System Site Name?
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
Site network fault alarms are sent to the specified mobile phone numbers of maintenance
engineers through SMS. After the system site name is changed, the new site name will be
displayed in the short message content (for example,
XXX site network fault
) so that
maintenance engineers will know the site where the fault has occurred.
Procedure
Step 1
Log in to the ECC500 WebUI.
Step 2
Choose
System Settings
>
Site Settings
.
Step 3
Modify
System Site Name
.
Step 4
Click
Submit
Figure 7-14
Changing the system site name
----End