![Huawei ATN 910C-G Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/huawei/atn-910c-g/atn-910c-g_quick-installation-manual_169314005.webp)
Site Requirements
3
To ensure personal and equipment safety, observe all the safety
precautions on the equipmentand in this document.
and and items do not cover all the safety precautions and
are only supplementary to the safety precautions.
The device needs to be installed in a clean, dry, well ventilated, and
temperature-controllable standard equipment room.In addition, the
equipment room must be free from leaking or dripping water, heavy
dew, and condensing.
Dustproof measures must be taken in the installation site. This is
because dust will cause electrostatic discharges on the device and affect
connections of metal connectors and joints, shortening the service life
of the device and even resulting in device failures.
The installation site must be free from acidic, alkaline, and other types
of corrosive gases.
The device that is operating may cause radio interference. If this is the
case, relevant measures may be needed to reduce the interference.
Generally, devices such as wireless antennas should not be installed in
the equipment room. If such devices must be installed indoors, ensure
that the electromagnetic environment meets relevant requirements or
take necessary electromagnetic shielding measures.
The device to be installed must be used indoors. To ensure normal
operation and long service life of the device, the following requirements
must be met:
The temperature and humidity in the installation site must meet device
requirements described in the following table.
Long-term operating
temperature [°C]
Relative operating
humidity [RH]
–40°C to +65°C
≤ 4000 m (For the altitude in the range of 1800 m to
4000 m, the operating temperature ofthe device
decreases by 1°C every time the altitude increases
by 220 m.)
Item
Requirements
Storage temperature
[°C]
–40°C to +70°C
Relative storage
humidity [RH]
Long-term operating
altitude [m]
Storage altitude [m] < 5000 m
OptiX PTN 916-F: Long-term: 10% to 90% RH,
non-condensing Short-term: N/A
Other devices: Long-term: 5% to 85% RH,
non-condensing Short-term: N/A
OptiX PTN 916-F: 10% to 100% RH, non-condensing
Other devices: 5% to 100% RH, non-condensing