No.
Description
2
The ground cable cannot be routed overhead, but should be buried in the earth or
arranged indoors.
3
Do not connect two cables together to extend the PGND cable, or add any switch or
fuse.
4
The PGND cable should be an alternating yellow and green plastic insulating one
with copper core.
5
The neutral line of the AC power cable cannot be connected to the protection ground
of transmission and communication equipment in the equipment room.
6
The length of the PGND cable should not exceed 45 m (147.64 ft). The PGND cable
should be as short as possible.
5.4 Engineering Labels for Cables
An engineering label serves as an identifier for on-site installation and maintenance after the
installation. Labels on the cables facilitate correct and orderly connection of cables, and easy
maintenance after installation.
Specialized for power cables and signal cables, the types of engineering labels are as follows:
l
The signal cables include network cables, optical fibers, and user cables.
l
The power cables include the AC power cables and DC power cables.
NOTE
Fill in the label according to the user's requirements if the user needs an integrated description of the label.
Make a relevant statement in the self-check report.
5.4.1 Introduction to Labels
Label Materials
Features:
l
Thickness: 0.09 mm (0.004 in.)
l
Color: chalk white
l
Material: polyester (PET)
l
Ambient temperature: -29°C (-20.2°F) to +149°C (300.2°F)
l
Compatible with laser printing and handwriting with markers
l
Pass UL and CSA authentication
Huawei AP8030DN & AP8130DN
Hardware Installation and Maintenance Guide
5 Appendix
Issue 02 (2014-12-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
100