Figure 4-33
Advanced Param. screen 3
Figure 4-34
Advanced Param. screen 4
System capacity (kVA)
Rated system capacity, equals to capacity of each power module multiplied by the
number of requisite power modules. The
Module quantity mismatch
alarm will be
generated if the setting is incorrect.
Power module capacity (kVA)
Rated power module capacity.
Requisite modules
Matches the system capacity.
Redundant modules
Set in accordance with loading capacity and redundant requirements.
Working mode
The value can be
Normal mode
(default),
Converter mode
,
Self-load mode
, or
ECO
.
BSC mode
−
The value can be
Non-BSC mode
(default) or
BSC mode
. The latter is set when the