![Huawei 0K-F120 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/huawei/0k-f120/0k-f120_user-manual_169589046.webp)
UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
37
The UPS can generate large leakage currents. A circuit breaker that provides leakage
current protection is not recommended.
If multiple UPSs are to be connected in parallel, input and output power cables for each
UPS should have the same length and specifications.
, the mains input power cable diameter of the UPS5000-E-240 kVA is less than
that of the UPS5000-E-200 kVA. The following describes the reason: Cables for the
UPS5000-E-(40 kVA-200 kVA) can be multi-core or single-core while those for the
UPS5000-E-(240 kVA-320 kVA) can only be single-core (single-core cables endure
currents better than multi-core cables).
lists the recommended cross-sectional areas for power cables.
Table 3-3
Recommended cross-sectional areas for power cables
Item
UPS5000-E-120K-F120
UPS5000-E-200K-
F200
UPS5000-E-320K-F320/UPS500
0-E-320K-F320T
40
kVA
80
kVA
120
kVA
160
kVA
200 kVA 240 kVA 280 kVA 320 kVA
M
ai
ns
in
pu
t
Mains input
current (A)
71
142
213
284
355
426
498
569
Recom
mended
cross-se
ctional
area
(mm
2
)
L1
4 x 16
4 x 50
4 x 95
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
70)
(Cable
types are
different.
)
2 x (4 x
95)
2 x (4 x
120)
L2
L3
N
B
yp
as
s
in
pu
t
Bypass input
current (A)
61
122
182
243
304
365
425
486
Recom
mended
cross-se
ctional
area
(mm
2
)
L1
4 x 16
4 x 35
4 x 70
2 x (4 x
50)
2 x (4 x
70)
2 x (4 x
70)
2 x (4 x
70)
2 x (4 x
95)
L2
L3
N
O
ut
pu
t
Output current
(A)
61
122
182
243
304
365
425
486
Recom
mended
cross-se
ctional
area
(mm
2
)
U
4 x 16
4 x 35
4 x 70
2 x (4 x
50)
2 x (4 x
70)
2 x (4 x
70)
2 x (4 x
70)
2 x (4 x
95)
V
W
N (If
the
volta
ge is