HTP Superstor Ultra SSU-119CN Скачать руководство пользователя страница 6

lp-730 Rev. 000 Rel. 000 Date 11.26.19

6

NOTE: TANK RECOVERY FROM COLD START WILL BE BETWEEN 10-13 MINUTES WHEN SIZED WITH CORRECT FLOW RATE, BOILER SIZE AND

PRESSURE DROP RATINGS FROM LIST IN ABOVE CHART.

*DOE TEST METHOD BASED ON 90  F TEMPERATURE RISE, 50  /140  W/BOILER WATER AT 180  F

LP-730-A

11/26/19

SUPERSTOR ULTRA

MODEL HEAT EXCHANGER 

SURFACE/VOLUME

PRESSURE 

DROP (FT.)

TEST 

PRESSURE

WORKING 

PRESSURE

180  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

200  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

180  F 

BOILER 

BTU/SIZE

200  F 

BOILER 

BTU/SIZE

RECOMMENDED 

FLOW RATE

140  F 115  F 140  F 115  F

SSU-20N

15 SQ. FT./1.,5 GAL.

6.0

300 PSI

150 PSI

121

168

136

185

84,000

87,000

8

SSU-30N

154

212

172

234

102,000

117,000

SSU-30LBN

169

234

189

257

114,000

131,000

SSU-45N

20 SQ. FT./2.0 GAL.

7.9

212

292

237

322

141,000

161,000

10

SSU-60N

266

370

298

405

174,000

198,000

SSU-80N

34 SQ. FT./3.0 GAL.

9.1

330

440

370

503

212,000

241,000

12

SSU-119N

11.3

423

564

474

645

269,000

301,000

14

SUPERSTOR ULTRA COMMERCIAL

MODEL

HEAT EXCHANGER 

SURFACE/VOLUME

PRESSURE 

DROP (FT.)

TEST 

PRESSURE

WORKING 

PRESSURE

180  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

200  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

180  F 

BOILER 

BTU/SIZE

200  F 

BOILER 

BTU/SIZE

RECOMMENDED 

FLOW RATE

140  F 115  F 140  F 115  F

SSU-45CN

40 SQ. FT./4.0 GAL.

6.8

300 PSI

150 PSI

314

414

351

477

215,000

246,000

20

SSU-60CN

9.2

354

467

396

539

245,000

270,000

22

SSU-80CN

68 SQ. FT./6.0 GAL.

10.0

490

647

548

745

331,000

374,000

24

SSU-119CN

12,7

637

841

713

970

425,000

490,000

28

SUPERSTOR ULTRA DOUBLEWALL

MODEL

HEAT EXCHANGER 

SURFACE/VOLUME

RECOMMENDED 

FLOW RATE 

(GPM)

PRESSURE 

DROP (FT.)

TEST 

PRESSURE

180  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

200  BOILER 

WATER FIRST 

HOUR RATINGS 

(GAL) *

180  F 

BOILER 

BTU/SIZE

140  F 115  F 140  F 115  F

SSU-45DWN

15 SQ.FT/1.5 GAL

6

8.2

300 PSI

40

63

70

108

107,000

SSU-60DWN

7

12.8

50

76

90

144

176,000

SSU-80DWN

10

13.6

72

113

138

215

208,000

SSU-119DWN

12

15.9

110

171

210

326

231,000

Table 2 - Specifications

Continuous Flow Performance Calculation

 

First Hour Rating - (.75 X Tank Capacity) = Continuous Flow

 

Example: SSU-45CN = 314 - (.75 X 45) = 280.25

B. Performance and Sizing Guidelines

NOTE:

 The table below describes the minimum BTU/H required to achieve the listed first hour rating. 

MODEL

GROSS BOILER OUTPUT

140

o

F

90

o

F Δ T

127

o

F

77

o

F Δ T

115

o

F

65

o

F Δ T

SSU-20N

84,000

121

140

168

SSU-30N

102,000

154

180

212

SSU-30LBN

113,000

169

198

234

SSU-45N

141,000

212

248

292

SSU-45CN

215,000

314

367

414

SSU-60N

174,000

266

311

370

SSU-60CN

245,000

354

414

467

SSU-80N

212,000

330

386

440

SSU-80CN

331,000

490

573

647

SSU-119N

269,999

423

495

564

SSU-119CN

425,000

637

745

841

Table 3 - Water Heater Performance and Sizing Guidelines

Содержание Superstor Ultra SSU-119CN

Страница 1: ...ubstantial property damage severe personal injury or death The manufacturer reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in...

Страница 2: ...for service 24 front 6 top and 0 sides are recommended service clearances A combustible door or removable panel is acceptable front clearance This water heater has been approved for closet installati...

Страница 3: ...ces sources generating heat 100o F 37o C or greater such as stove pipes space heaters etc may damage plastic components of the water heater as well as plastic vent pipe materials Such damages ARE NOT...

Страница 4: ...ty damage and could result in serious personal injury or death This water heater is certified for indoor use only DO NOT INSTALL OUTDOORS Outdoor installations ARE NOT covered by warranty Choose a loc...

Страница 5: ...30N 34 39 1 2 30 GAL 62 LBS SSU 30LBN 22 28 1 2 23 1 4 71 LBS SSU 45N 46 52 1 2 19 1 4 45 GAL 72 LBS SSU 60N 23 1 4 60 GAL 1 NPTM 109 LBS SSU 80N 6 29 64 3 4 72 80 GAL 1 1 2 NPTM 143 LBS SSU 119N 7 1...

Страница 6: ...F 140 F 115 F SSU 45CN 40 SQ FT 4 0 GAL 6 8 300 PSI 150 PSI 314 414 351 477 215 000 246 000 20 SSU 60CN 9 2 354 467 396 539 245 000 270 000 22 SSU 80CN 68 SQ FT 6 0 GAL 10 0 490 647 548 745 331 000 37...

Страница 7: ...0 60 83 99 101 SSU 30LBN A 53 80 111 133 135 150 B 40 60 83 99 101 112 SSU 45N A 53 80 111 133 135 150 159 186 187 B 40 60 83 99 101 112 119 139 140 SSU 60N A 133 135 150 159 186 187 212 231 B 99 101...

Страница 8: ...local water treatment companies for other treatment solutions to reduce this affect NOTE Topromoteapplianceservicelife itisstronglyrecommended to follow the maintenance procedures in this manual Part...

Страница 9: ...d a cap or plug into the relief valve or relief valve line under any circumstances Explosion and property damage serious injury or death may result RE INSPECTION OF T P RELIEF VALVES T P valves should...

Страница 10: ...11 77 12 24 12 7 13 1 10 GPM 10 25 11 1 11 95 12 8 13 66 12 GPM 11 3 13 2 14 1 15 16 14 GPM 15 3 16 4 17 5 18 6 19 8 Pressure Drop for Pipe Length of 1 1 4 Copper Six 90o Elbows and One Tee Pipe Size...

Страница 11: ...lators should have an integral flow check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system pipin...

Страница 12: ...3 All circulators should have an integral flow check 4 Drains and check valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate...

Страница 13: ...ck valve between heating appliance and water heater will assist in purging air from system 5 This drawing is meant to demonstrate system piping only The installer is responsible for all equipment and...

Страница 14: ...ler before starting any wiring procedures It is recommended that a disconnect switch be installed between the boiler control and the water heater Figure 16 Wiring with Circulators Figure 17 Wiring wit...

Страница 15: ...g with Circulators R845A Relay Figure 19 Zoning with Circulators Using R8182D and DPST No Relay Required Figure 20 Zoning with Circulators Using L8124 A C and R845A Relay Figure 21 Zoning with Circula...

Страница 16: ...A Relay Figure 24 Control with Built In DPST Switch No Relay Required Figure 22 Using L8148A or L8152A Cold Start Boiler Control with Circulators Figure 25 Zoning with Circulators Using L8124 E F and...

Страница 17: ...lp 730 Rev 000 Rel 000 Date 11 26 19 17 Figure 27 Priority Zone with Circulators Figure 28 Priority Zone with Zone Valves Figure 29 Using L8148A or L8152A Cold Start Boiler Control with Zone Valves...

Страница 18: ...uring there are no leaks within the system flush the system to clear any soldering residue Many soldering fluxes contain Zinc Chloride which can corrode stainless steel Draw at least three times the v...

Страница 19: ...e Replace if valve is blocked or does not operate properly NOTE TAKE CAUTION WHEN OPERATING RELIEF VALVE DISCHARGED WATER MAY PRESENT A SCALD RISK Drain Valve Open the drain valve and drain a few quar...

Страница 20: ...r Trap in Loop Purge Air Not Enough Hot Water Zone valve restriction 1 full bore replace zone valve Circulator arrow reversed Reverse circulator Tank temperature too low Raise tank temperature Boiler...

Страница 21: ...that repair replacement or refund are the exclusive remedies of the Owner OWNER RESPONSIBILITIES The Owner or Qualified Installer Service Technician must 1 Have a relief valve bearing the listing mark...

Страница 22: ...re of the piping near the product e For gas fired products a picture of the venting including how it exits the building All claims will be reviewed by HTP within three 3 business days If additional in...

Страница 23: ...te of Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer IMPORTANT Customer Please only sign a...

Отзывы: