Description/Part #
Inlet Water Filter / 7850P-017
Check Point
(Main PCB)
N/A
Function
This component consists of durable STS, PPS material for filtering out debris and heavy
metals.
Failure Event
Input capacity of cold water is not constant and thermal efficiency is poor.
Effects
Noise at the heat exchanger is generated and pipes are blocked by the debris.
Error Code
N/A
Diagonostic
Clean the Cold water inlet filter.
Color / Wire Number
N/A
Description/Part #
Flow Control Valve / 7850P-053
Check Point
(Main PCB)
CN 14, CN 3
Function
The component detects water flow and regulates water flow rate in order to supply
stable hot water (More than 0.5 GPM).
Failure Event
Water flow rate is not detected and water leakage occurs around the flow control valve.
Effects
① Ignition sequence does not start.
② Operation of product is stopped once water leakage is detected.
Error Code
Er 65
Diagonostic
① Restart the unit
② Check the connection around the flow control valve.
Color / Wire Number
[IWM (Inlet Water Modulation)]
GND (yellow) : connector ①
IWM Stepper motor position (green) : connector②
VDD (white) : connector ③
IWM Stepper motor coil X phase (red) : connector ④
IWM Stepper motor coil Y phase (black) : connector ⑤
VDD (blue) : connector ⑥
IWM Stepper motor coil /X phase (orange) : connector ⑦
IWM Stepper motor coil /Y phase (brown) : connector ⑧
1. PPS material Body
2. Hall sensor rated voltage
DC5~24V 10mA. Max
3. Operating Fluid :
0℃~80℃ (32 ~ 176℉)
4. Operating range :
1.2 ~ 30ℓ (0.32 ~ 8 gpm)
VCC (red) : connector
④
Water flow sensor (white) : connector
⑤
GND (blue) : connector
⑥
Inlet water filter
① ② ③ ④ ⑤ ⑥
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
① ② ③ ④ ⑤ ⑥ ⑦ ⑧