63
LP-520 REV. 5.1.17
4. At initial fill and during appliance startup and testing, check system thoroughly for leaks. Repair all leaks before proceeding further.
Eliminate all system leaks. Continual fresh make-up water will reduce appliance life. Minerals can build up in the heat exchanger,
reducing heat transfer, overheating the heat exchanger, causing heat exchanger failure and possibly resulting in property damage,
severe personal injury, or death.
5. The system may have residual substances that could affect water chemistry. After the system has been filled and leak tested, verify
that water pH and chlorine concentrations are acceptable by sample testing.
It is important to purge the system of air to avoid damage to the appliance.
E. PURGE AIR FROM CH AND INTERNAL STORAGE TANK
IMPORTANT!
While commissioning the system, the air vent on top of the appliance must remain fully open to allow the appliance to
properly fill. Failure to keep the air vent open could lead to improper appliance and system operation.
To purge air from the system:
a. Connect a hose to the purge valve and route hose to an area where water can drain and be seen.
b. Close the appliance or system isolation valve between the purge valve and fill connection to the system.
c. Close zone isolation valves.
d. Open quick-fill valve on cold water make-up line.
e. Open purge valve.
f. Open the isolation valves one zone at a time. Allow water to run through the zone, pushing out the air. Run water until no
noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all
zones are purged.
g. Close the quick-fill water valve and purge valve and remove the hose. Open all isolation valves. Watch the system pressure
rise to correct cold-fill pressure. It is recommended that you put the pumps into manual operation to assist in purging the
circuits.
h. Disconnect the wires that are connected to the THERMOSTAT terminals of the terminal block. Apply power to the
appliance. After the control goes through the start-up sequence, the display will turn off.
i. Press and hold the
button for five seconds. Then scroll to 29:AP by turning the dial
. Press the
button. AP:cP will
show on the display. Press the
button to change the test time. The default is five minutes. Turn the dial
counterclockwise to lower or clockwise to raise the displayed value. Press the
button again to save any changes.
j. Then use the dial
to scroll to cP:off. Press the
button to turn on test mode. Turn the dial
counterclockwise to
lower or clockwise to select on. Press the
button again to start test mode.
k. The CH and internal circulation pumps will come on. Run pumps as required to help bleed out all entrapped air. Some good
indicators that air is removed include the absence of gurgling noises in the pipes and pump operation becoming very quiet.
Test mode will stop automatically after the set time (default is five minutes), or press the
button to leave it manually.
l. After the system has operated for some time, eliminate any residual air by using the manual air vents located throughout the
system.
m. If purge valves are not installed in the system, open manual air vents in the system one at a time, beginning with the lowest
floor. Close vent when water squirts out. Repeat with remaining vents.
n. Refill to correct pressure.
F. PURGE AIR FROM DHW SYSTEM
1. Make sure CH and DHW lines to the appliance are open and full of water. Turn on all electric power to appliance.
Ensure the appliance is full of water before firing the burner. Failure to do so will damage the appliance. Such damage IS NOT covered
by warranty, and could result in property damage, serious personal injury, or death.
2. Open hot water faucets in the DHW system. Start with the faucets nearest the appliance.
3. Keep faucets open until water runs freely and all air is purged. Then move on to faucets further away from the appliance in the
system.
Содержание EFTC-140W
Страница 2: ...2 LP 520 REV 5 1 17 ...
Страница 36: ...36 LP 520 REV 5 1 17 Figure 24 Piping Legend ...
Страница 45: ...45 LP 520 REV 5 1 17 Figure 32 Electrical Wiring Diagram ...
Страница 46: ...46 LP 520 REV 5 1 17 Figure 33 Ladder Diagram ...
Страница 88: ...88 LP 520 REV 5 1 17 MAINTENANCE NOTES ...