16 

 

HOLDING REGISTERS 

DEFINITION 

VALUE 

ACTION 

40001 

Configuration 

00 04 

Set configuration to read 40003 

40003 

Rate Command 

00 00 

Sets modulation % 

Table 16 

Register 40003 needs to receive the rate command as follows: Acceptable rang is 0 to 100. Value needs to be greater than 15 
for the boiler to fire. When the command is 16, the boiler will run at minimum fan speed (firing rate). When the command is 
100 the boiler will run at max fan speed (firing rate). If the command value is anywhere between 16 and 100, the boiler will run 
at a fan speed proportional to the command sent between minimum and maximum firing rates. 

NOTE:

 To ensure proper operation, resend the configuration bits to holding register 40001 prior to issuing a command. For proper 

hexadecimal conversion of rate percentage, please refer to the rate and temperature conversion section of this manual. 

2. SEND TEMPERATURE COMMAND FROM MASTER 

In this configuration, the appliance is controlled by setting the boiler temperature via the Modbus adapter. The temperature range is the 
range of the value of Installer Parameter 12 (all except Elite) or Function 12 Min Boiler Temp on the Elite, and the temperature setting 
of the CH value on the User Menu (all except Elite) or CENTRAL HEAT setting on the Elite. All sensors and limiting devices (excluding 
the 0-10 Vdc signal, which will be sent to the Modbus) should be hardwired to the terminal strip on the appliance. 
 
For this command to function on Munchkin and Mod Con models, Installer Parameter 16 needs to be set at 2 and Installer Parameter 
17 needs to be set at 0. On Elite models, Function 16, Optional Input must be set to 0-10 volt and Function 17 0-10 volt function must 
be set on Temperature. 
 

NOTE:

 The holding registers are same as above, in Table 15. 

 

Register 40003 needs to receive the rate command as follows: Acceptable rang is 0 to 100. Value needs to be greater than 15 
for the boiler to fire. When the command is 16, the boiler will run at minimum temperature (value of Installer Parameter 12 
above). When the command is 100 the boiler will run at maximum temperature (CH temperature above). If the command value 
is anywhere between 16 and 100, the boiler will run at a temperature proportional to the command sent between minimum and 
maximum temperatures described above. 

NOTE:

 To ensure proper operation, resend the configuration bits to holding register 40001 prior to issuing a command. For proper 

hexadecimal conversion of rate percentage, please refer to the rate and temperature conversion section of this manual. 

D. EXAMPLE #3 

– HOT WATER GENERATION 

Hot water generation can be accomplished using one of two methods when an appliance is connected to a BAS system, DHW with 
direct control, and DHW with remote control. 
 

DHW WITH DIRECT CONTROL 

This is the typical installation with a hot water generator in close proximity to the appliance with the tank thermostat, or tank temperature 
sensor, wired to the terminal strip of the appliance 
 

DHW WITH REMOTE CONTROL 

This installation may or may not have the hot water generator in close proximity to the appliance. Its sensors and thermostat values are 
only available through the Modbus communication bus. 
 
To ensure that the appliance can properly respond to a call for hot water generation, the following holding registers must be set in 
addition to other commands: 
 

HOLDING REGISTERS 

DEFINITION 

VALUE 

ACTION 

40001 

Configuration 

00 1A 

Set configuration to read 40002, 4 and 5 

40002 

Coils 

00 10 

Enables tank Tstat 

(00 00 disables appliance)

 

40004 

Tank set point 

0# ## 

Sets set point 

40005 

Tank Temperature 

0# ## 

Passes tank temp from remote sensor 

Table 17 

NOTE: 

To ensure proper operation, resend the configuration bits to holding register 40001 prior to issuing a command. For proper 

hexadecimal conversion of rate percentage, please refer to the rate and temperature conversion section of this manual. 

E. CASCADE 

In order to operate the appliance in cascade with Modbus communications, configure the master appliance. Connect the remaining 
appliances in the cascade through the normal cascade communications wiring. Cascade control can then be accomplished 
automatically through the master appliance. 
 

Содержание 7350P-629

Страница 1: ... WITH MODCON MODCON VWH PIONEER VERSA FLAME MANUFACTURED ON OR AFTER JULY 1 2011 FOR USE WITH ELITE ELITE VWH MANUFACTURED ON OR AFTER AUGUST 1 2011 NOTICE HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE ...

Страница 2: ...iances FOR THE INSTALLER The installer should be guided by the instructions furnished with the Modbus local codes and utility company requirements Preference should be given to codes and requirements where they differ from the furnished instructions Additional publications which should guide the installer include The latest version of the National Electrical Code NFPA No 70 In Canada refer to Cana...

Страница 3: ...ROM MASTER 16 D EXAMPLE 3 HOT WATER GENERATION 16 E CASCADE 16 F RATE AND TEMPERATURE CONVERSIONS 17 G APPLIANCE STATUS CODES 19 PART 8 TROUBLESHOOTING 19 A PHYSICAL LAYER 19 B COMMUNICATIONS 19 C LED DIAGNOSTICS 19 D MODBUS ERROR CODES 19 INSTALLATION AND MAINTENANCE NOTES 20 HTP CUSTOMER INSTALLATION RECORD FORM 21 PART 1 GENERAL INFORMATION Modbus communication systems utilize a master follower...

Страница 4: ... heater equipped with a control with firmware revision MTSA P110414 or greater To determine whether your product is compatible with this adapter refer to Figure 1 3 Shielded twisted pair communication cable Figure 1 Controller Revision Label Location C DEFINITIONS Table 1 is a list of definitions used throughout this manual ABBREVIATION OR ACRONYM DEFINITION ASCII American Standard Code for Inform...

Страница 5: ...n be mounted on the side of the appliance OR the wall next to the appliance as long as care is taken to avoid components behind the mounting surface The mounting location must be within 3 feet of the appliance controller in order to be plugged into the controller programming port NOTE It is not recommended to install the Modbus adapter inside the appliance housing Doing so may affect appliance ope...

Страница 6: ...guration There is one jumper on the Modbus adapter When this jumper is in place factory default it connects a termination resistor across the data lines of the RS 485 connection Leave the jumper in if the Modbus adapter is at the end of the RS 485 bus Remove the jumper if the Modbus adapter is one of many connections and not at the end of the bus See Figures 2 and 3 Figure 3 Modbus Termination Jum...

Страница 7: ... have a unique address It is not recommended to use 1 as an address as this is often the default address for various other Modbus devices that may be on the bus In order to keep track of addresses for future maintenance purposes record all device addresses in the Installation and Maintenance Notes section included in this manual SAVE THIS DOCUMENT IN A SECURE LOCATION FOR FUTURE REFERENCE To set t...

Страница 8: ... OFF MODBUS DISABLED factory default 37 ON MODBUS ON 37 AUTOMATIC MODBUS AUTO enables automatic detection of a PC or Adapter Table 5 Parameter 37 Settings FUNCTION 37 Press ENTER once the desired setting is flashing on the display Once accepted the selection should not flash Please do not leave the Installer Menu Configure the Address Baud Rate and Parity settings described below B MODBUS ADDRESS ...

Страница 9: ...SETTING TEXT DISPLAY PARITY STOP BITS 1 ST No parity 1 stop bit 2 ST No parity 2 stop bits E PA Even parity 1 stop bit O PA Odd parity 1 stop bit Table 6 Parameter 40 Settings FUNCTION 40 Press ENTER The STOP PARITY value will blink Use the UP and DOWN arrows to toggle between 1 ST 2 ST E PA and O PA Make your selection based on the table above Press ENTER again to select the STOP PARITY value and...

Страница 10: ...d input registers 5 05 Force single coil 6 06 Preset single register 7 07 Read exception status 8 08 0 00 Diagnostic Return query data 1 01 Diagnostic Restart communication 2 02 Diagnostic Return diagnostic register 4 04 Diagnostic Force listen mode 10 0A Diagnostic Clear counters and diagnostic registers 11 0B Diagnostic Return bus message count 12 0C Diagnostic Return bus exception error count 1...

Страница 11: ...d the request but will take a significant amount of time to process it This response prevents a timeout error 06 FOLLOWER DEVICE BUSY This is received when a follower device is busy processing a programmed command User should query this device at a later time 08 MEMORY PARITY ERROR The server or follower attempted to read a file but detected a parity error in the memory The user can retry the requ...

Страница 12: ...ance 5 burning 0 1 on 0 off 0 1 1 10055 Appliance 6 burning 0 1 on 0 off 0 1 1 10056 Appliance 7 burning 0 1 on 0 off 0 1 1 10057 Appliance 0 lockout same as 10034 0 1 on 0 off 0 1 1 10058 Appliance 1 lockout same as 10042 0 1 on 0 off 0 1 1 10059 Appliance 2 lockout 0 1 on 0 off 0 1 1 10060 Appliance 3 lockout 0 1 on 0 off 0 1 1 10061 Appliance 4 lockout 0 1 on 0 off 0 1 1 10062 Appliance 5 locko...

Страница 13: ...upply temperature 0 Deg F 76 266 0 1 30043 Appliance 6 firing rate 0 0 100 1 30044 Appliance 6 status 0 NA 0 65535 30045 Appliance 6 lockout code NA 0 65535 30046 Appliance 7 supply temperature 0 Deg F 76 266 0 1 30047 Appliance 7 firing rate 0 0 100 1 30048 Appliance 7 status 0 NA 0 65535 30049 Appliance 7 lockout code 0 NA 0 65535 30050 Discrete inputs 49 64 0 NA 0 65535 30051 NTC 6 temperature ...

Страница 14: ...uring programming 207 Parameter EEPROM failure 190 S1 maximum temperature 191 S2 maximum temperature 192 S1 shorted 193 S1 interrupted 194 S2 shorted 195 S2 interrupted 196 Low water lockout 197 Flue sensor shorted 198 Flue sensor interrupted 199 Low water lockout 2 185 ECS6 temperature lockout 186 ECS7 temperature lockout Table 12 E STATUS CODES STATUS CODES INPUT REGISTERS 30014 30023 30028 3003...

Страница 15: ...ures or commands The master should update temperature registers at least once per minute but no more than once per second B EXAMPLE 1 In this configuration the appliance is controlled by setting the set points locally on the appliance and providing an enable signal through Modbus communications All sensors and limiting devices excluding the thermostat enable and tank thermostat enable signals whic...

Страница 16: ...re value of Installer Parameter 12 above When the command is 100 the boiler will run at maximum temperature CH temperature above If the command value is anywhere between 16 and 100 the boiler will run at a temperature proportional to the command sent between minimum and maximum temperatures described above NOTE To ensure proper operation resend the configuration bits to holding register 40001 prio...

Страница 17: ...ters or some scientific calculators For example RATE HEX 0 00 20 14 45 2D 60 3C 80 50 95 5F 100 64 Table 18 Temperature Conversions To send a desired set point the hexadecimal value must be determined through linear interpolation of programmable parameters on the BMS setup menu BMS temperature set point at low analog input BMS temperature set point at high analog input These variables set the temp...

Страница 18: ...7 27 130 3F 163 57 98 28 131 40 164 58 99 29 132 41 165 59 100 2A 133 42 166 5A Temperature The Modbus adapter passes temperature data to the appliance in degrees Fahrenheit Also to accommodate decimal places the decimal value must be divided by 10 The data sent over the Modbus is passed as an unsigned 16 bit integer This poses no problem unless the data becomes negative such as temperatures below...

Страница 19: ...ateway BAS master 3 Check for broken wires 4 Check A B terminal connections 5 Check for terminating resistors 120 ohms at each end of the RS 485 bus only 6 Check all wire lengths Are any drops too long 7 Check proper shield grounding B COMMUNICATIONS 1 Verify controller is configured for MODBUS AUTO or ON 2 Check baud rate 9600 19200 3 Check parity 4 Check Modbus address 5 Check port setting on ma...

Страница 20: ...mand 4 Check configuration bits for holding register 40001 5 Check commands and data for holding registers 40002 40007 INSTALLATION AND MAINTENANCE NOTES _________________________________________________________________________________________ ...

Страница 21: ...ler s Code Name Product Serial Number s Modbus Adapter Address As Configured by the Installer Comments Installer s Phone Number Signed by Installer Signed by Customer IMPORTANT NOTES Customer Please only sign after the installer has reviewed the installation safety proper operation and maintenance of the system In the case that the system has any problems please call the installer If you are unabl...

Отзывы: