26
WFS 101545 Operations Manual
ALARM DISMISS
To dismiss or ignore a particular alarm move the associated slide
switch to “ON” position by touching the “ON” side of the image. This will
permanently silence the alarm and ignore the fault.
CAUTION:
The alarm condition still exists. There is no longer a warning of the faulty
condition.
LEAK DETECTED
A LEAK DETECTED alarm will also initiate an ALL STOP command
shutting down all pumps and the chiller. This is to protect against a broken line.
However, it may be accidentally tripped during normal filter change. To prevent
potential process interruption during a filter or resin bed change set the bottom
slide switch to “ON” during those operations.
f.
Resitivity Sensors
Two (2) Resilite RES7130 resistivity sensors are
provided to monitor water condition to the Process
Circuit. These sensors have a fixed setting of 1 Meg
Ohm. They will indicate resistivity in excess of 1 Meg
Ohm with a green light. If resistivity becomes less
than 1 Meg Ohm the light will change to red.
These sensors provide an indication as to when to
change out the customer supplied resin beds. See
figure 5-10
6
FILTER HOUSING AND FILTER ELEMENT CHANGE OUT
The system utilizes four stainless steel filter housings. The housings are rated for a nominal 60
PSI at 110
o
F with a flow rate of 50 GPM. See Figure 5-11
WARNING:
For use with water only
Do not exceed 100 PSI
Do not use with air or gasses
Do not use with flammable liquids
FIGURE 5-10