Page 15
5.2.
Panel states
HST-HP201-2 has 7 different panel states.
Init & Stop state: This panel mode is valid at power up while panel is intializing its
modules and when panel is doing restore for all its default data. Any fire or fault
conditions will happen in this phase will be ingnored by the panel.
Scan state: This panel mode is valid at scaning phase after power up or when loops
auto learn is requested from programming menus. Only loops fault and loop devices
fault will be triggered after scanning is finsihed. Any other fire or fault conditions
will be ignored.
PC state: This panel mode is valid when computer software starts to update part or all
of panel configuration data. Panel will not enter PC mode if it has one or more fire
conditions. If panel has one or more fault conditions, it will do automatically fire
reset. Any new fire or fault conditions will be ignored by the panel. LCD displays PC
mode window. Panel will restart itself after computer software finishes its update
within the panel.