INSTALLATION AND MAINTENANCE INSTRUCTIONS

HM201-SC

Addressable Short Circuit Isolator Module

SPECIFICATIONS

Nominal Operating Voltage::        15 to 28 VDC
Short Circuit Current Limitation     

>

700 mA @ 24 VDC

Short Loop Resistance             

<

50

Ω

Operating Humidity Range:        10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range:

   -10°C to50°C

Dimension:

                   120 mm L x 80mm W x 43mm H 

Weight:                        175 g

INSTALLATION WIRING

Terminal Description

T14- Loop Input+
T15- Loop Input-
T3- Loop 
T2- Loop Output-

BEFORE INSTALLING

This   information   is   included   as   a   quick   reference
installation guide. Refer to the control panel installation
manual for detailed system information. If the modules
will be installed in an existing operational system, inform
the operator and local authority that the system will be
temporarily   out   of   service.   Disconnect   power   to   the
control panel before installing the modules.

NOTICE:

  This   manual   should   be   left   with   the

owner/user of this equipment.

GENERAL DESCRIPTION

The   Short   Circuit   Isolator   Modules   enable   part   of   the
communications loop to continue operating when a short
circuit occurs on it. An LED indicator turns on during a
short   circuit   condition.   The   module   will   automatically
restore   the   entire   communications   loop   to   the   normal
condition when the short circuit is removed.

L +

L -

L O O P   I N P U T +

L O O P   I N P U T -

L O O P   O U T P U T +

L O O P   O U T P U T -

L +

L -

©