HST HD201B Скачать руководство пользователя страница 3

HLogic Security Technology Co., Ltd

www. hstfire .com

Document Ref: M1215-04

Issue: 5.5

01/2017

Maintenance

Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance

and will be temporarily out of service.

1. Counterclockwise rotation detector, remove it from the mounting base is removed.

2. Remove the detector cover by pressing firmly on each of the four removal tabs that hold the cover in place.

3. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip

to Step 7.

4. Remove the chamber cover/screen assembly by pulling it straight out.

5. Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.

6. Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in

place.

7. Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place.

8. Reinstall the detector.

9. Test the detector as described in TESTING.

10. Reconnect disabled circuits.

11. Notify the proper authorities that the system is back on line.

Remove the detector from base.

Remove the detector cover

Remove the chamber from detector

To clean the chamber

HLogic Security Technology Co.,Ltd,

B1-4F XinHaoSheng High Tech Park,YongHe Rd,Baoan,SZ,China

17

1115CPR2016-06-10

EN54-7

HD201B Addressable smoke detector

Fire detection and fire alarm systems installed in and around buildings.

According to Construction Products Regulation EU N° 305/2011

17

0359

Отзывы: