HLogic Security Technology Co., Ltd
www. hstfire .com
Document Ref: M1215-04
Issue: 5.5
01/2017
Maintenance
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance
and will be temporarily out of service.
1. Counterclockwise rotation detector, remove it from the mounting base is removed.
2. Remove the detector cover by pressing firmly on each of the four removal tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip
to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in
place.
7. Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
Remove the detector from base.
Remove the detector cover
Remove the chamber from detector
To clean the chamber
HLogic Security Technology Co.,Ltd,
B1-4F XinHaoSheng High Tech Park,YongHe Rd,Baoan,SZ,China
17
1115CPR2016-06-10
EN54-7
HD201B Addressable smoke detector
Fire detection and fire alarm systems installed in and around buildings.
According to Construction Products Regulation EU N° 305/2011
17
0359